The discharging characteristics of direct evaporation internal melt ice-on-vertical-coil thermal storage air conditioning system
Qing Chunyao,Gao Rixin,Gao Qinghua,Zhou Zhiming,Feng Ziping,Liu Zhenyu,Cui Changxue,Zhang Xiaolan,Du Guanglin
DOI: https://doi.org/10.3969/j.issn.1001-7100.2009.08.009
2009-01-01
Abstract:A mathematical model on the discharging process of direct evaporation internal-melt ice-on-vertical-coil thermal storage air conditioning system was developed,which based on the principle of serial heat transfer resistances and energy conservation.The ice melting characteristics were analyzed theoretically.Calculation results illuminates that refrigerant temperature at the outlet of the ice-coil rises with time,but a gentle drop of the temperature is found at the melting finishing period,because the cylindrical ice surrounding the coil breaks up and floats,which results in the natural convection enhancement instantaneously.On the other hand,during the melting process,the heat transfer coefficient decreases sharply first,then maintains stable,and increases fast finally.A conclusion was gained that the phenomena was related to the diameter of the water ring formed as ice melting,and the discharging velocity decreased when the ring diameter grew up.The model's reasonability and reliability is verified by the experimental data.