Comparison of Cooling Load Between Radiant Slab and Air Systems in Large Space Buildings with Solar Radiaiton

Haida Tang,Tao Zhang,Xiaohua Liu
2018-01-01
Abstract:In this study, through a harmonic method we derive the analytical solution of the dynamic cooling load for a radiant slab system and air system in a large pace building with high-intensity solar radiation. The results indicate that peak value of the cooling load of a radiant system in a 24h operation is slightly larger than the air system because the conventional slab floor has a larger decay rate and time lag for the direct solar radiation than the radiant slab. However, the cooling load difference between the two systems is less than 10 W/m(2) (3.17 Btu/ ft(2)h).