Stability and Maximum Output Capacity of Grid Connected VSC under Wide Operating Range

Yuting Zheng,Chunming Tu,Weijie Xie,Fan Xiao,Qi Guo,Pingjuan Ge
DOI: https://doi.org/10.1109/spies55999.2022.10082194
2022-01-01
Abstract:In weak grids, frequency oscillations caused by voltage source converters (VSCs) pose a great challenge to the safe and stable operation of power systems. Due to the stochastic and intermittent nature of renewable energy, the operating point of grid-connected systems is more susceptible to external factors. As a result, the stability of the system changes continuously with the migration of the operating point, and traditional stability analysis methods based on a single operating point become no longer applicable. To obtain the system stability domain under full operating range, a VSC current loop multiple-input multiple-output (MIMO) small-signal model with introducing operating points as variables is established, which takes into account the multiple coupling effects between the dq axes and the dynamic changes of the phase-locked loop (PLL). Based on the proposed model, the stable operating domain of the system is obtained, as well as the influence law of the system impedance parameters on this domain. Simulation results are given to validate the effectiveness of the model and the theoretical analysis.