Orthogonal Experiment of Research on Coordinated Control Method of Indoor Multiple Pollutants V1

Yan Zhang
DOI: https://doi.org/10.17504/protocols.io.3byl4bxpjvo5/v1
2022-01-01
Abstract:Indoor air pollution in office buildings is complex and serious. This research is targeted at three types of air pollutants: CO2, VOCs, and PM2.5. In order to seek the optimalcontrol method to achieve good indoor air quality, an orthogonal experiment was carried out in the environmental chamber to compare the control time and energy consumption of four control methods (purifier+ and window+, purifier+ and window-, purified fresh air 240 m3/h and purified fresh air 400 m3/h) required for pollutants to meet the standard. The result shows that the purifier+ and window+ method is more effective in most conditions. Its control time is reduced by 8.06% and the energy consumption is reduced by 11.91% compared with the traditional control method of purified fresh air 240 m3/h. This research guides the optimization control strategy of indoor air quality under different pollution conditions in office buildings.
What problem does this paper attempt to address?