Analysis and Selection of Working Fluid for Marine Ejection-Compression Air-Conditioning System

Shengyu Li,Xiao Hu,Jun Lu
DOI: https://doi.org/10.1109/icpre55555.2022.9960387
2022-01-01
Abstract:This paper presents a modified dual-loop bi-evaporator ejection-compression cycle driven by marine waste heat dealing with the varying sensible and latent loads in different climates. Based on the constant-pressure mixing theory, a thermodynamic model is developed to investigate the effects of various parameters such as the generator, two evaporators and the condenser temperatures on the ejector behaviour and cycle performance. Eco-friendly refrigerants, such as R134a, R245fa, R600, R290, R1234yf, R1234ze(E), and R1233zd (E), are adopted as the working fluid. To assess the modified cycle performance, a new conception of global COP is introduced, where heat consumption and electric power are converted to the same grade before added together. The model results show good agreement with the corresponding experimental data, where the average deviation is 3.34%, and the deviation ranges from -9.93% to 7.46% for the ejector entrainment ratio. The results indicate that the highest global COP utilizing R1233zd(E) followed by that of R245fa, with the R1234yf system having the lowest value. Meanwhile, the condenser temperature of the hybrid refrigeration cycle has a great influence on the performance of the cycle. This paper is expected to provide a good reference for the utilizing prospect of R1233zd(E) and R245fa in ejector-compression refrigeration systems.
What problem does this paper attempt to address?