Optimization and Design of Basin-Type Insulator in ±550 Kv Hvdc GIS for Offshore Wind Platform

Yixuan Li,Boya Zhang,Xingwen Li,Kaixuan Li,Kai Ji,Zhenle Na,Xuan Yao
DOI: https://doi.org/10.2139/ssrn.4383656
2023-01-01
SSRN Electronic Journal
Abstract:High voltage direct current (HVDC) gas-insulated switchgear (GIS) plays a crucial role in reaching renewable energy and interconnection goals by enabling the economical connecting of far offshore wind farms and underwater cables. However, the charge accumulation on insulator surface hinders the development of DC GIS at higher voltage. Based on DC insulation testing, the design criteria for a ±550 kV DC insulator were proposed in this study. The electric field distribution and charge distribution of obtuse conical insulators, disk insulators, and conical insulators were investigated using a surface charge accumulation model. The results show that with increasing inclination of the insulator, the intersecting angle between the electric field line and insulator surface increases, leading to an increase in the normal electric field and charge accumulation at the gas-solid interface. With increasing insulator size, the tangential component of the electric field diminishes dramatically, whereas the normal component decreases slightly. In addition, the conical insulator should be larger in size than disk insulators and obtuse conical insulators to achieve the same level of insulation. Finally, optimum geometric constructions for ±550 kV DC GIS insulators were obtained.
What problem does this paper attempt to address?