Cooling Performance and Optimization of a Tubular Indirect Evaporative Cooler Based on Response Surface Methodology

Tiezhu Sun,Tingzheng Tang,Chuanjun Yang,Weichao Yan,Xin Cui,Junjie Chu
DOI: https://doi.org/10.1016/j.enbuild.2023.112880
IF: 7.201
2023-01-01
Energy and Buildings
Abstract:To optimize the cooling effectiveness of the tubular indirect evaporative cooler (TIEC), an experimental design was conducted using the response surface methodology (RSM). In this work, the wet-bulb effec-tiveness was selected as the response value, while the influencing factors included six operation param-eters, namely, the spray water flow rate (Qw), secondary-to-primary air flow rate ratio (Rsp), primary air resistance (R1), secondary air resistance (R2), inlet air dry bulb temperature (tg1) and air relative humidity (RH). The operation conditions of a TIEC with a tube diameter of 10 mm were optimized. The second-order model fitting of the RSM was used to obtain the polynomial regression equation between the wet-bulb effectiveness and each factor. The wet-bulb effectiveness can be achieved up to 78 % under the optimized conditions with Qw of 1.2 m3/h, Rsp of 0.5, R1 of 89 Pa, R2 of 100 Pa, tg1 of 17.3 degrees C, and RH of 79.6 %. (c) 2023 Elsevier B.V. All rights reserved.