Frost Jacking Characteristics of Transmission Tower Pile Foundations with and without Thermosyphons in Permafrost Regions of Qinghai–Tibet Plateau
Yalong Zhou,Xu Wang,Fujun Niu,Fei He,Chunxiang Guo,Deren Liu,Daijun Jiang,Yalong Zhou; Xu Wang; Fujun Niu; Fei He; Chunxiang Guo; Deren Liu; and Daijun Jiang1Ph.D. Candidate,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China. Email: 2Professor,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China (corresponding author). Email: publicwang@163.com3Professor,State Key Laboratory of Frozen Soil Engineering,Northwest Institute of Eco-Environment and Resources,Chinese Academy of Sciences,Lanzhou 730000,China. Email: niufujun@lzb.ac.cn4Associate Professor,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China. Email: hefei_2006@126.com5Associate Professor,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China. Email: guocx@mail.lzjtu.cn6Associate Professor,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China. ORCID: https://orcid.org/0000-0001-7519-8371. Email: liuderen@mail.lzjtu.cn7Associate Professor,School of Civil Engineering,Lanzhou Jiaotong Univ.,Lanzhou,Gansu 730070,China. Email: 13893603618@163.com
DOI: https://doi.org/10.1061/(ASCE)CR.1943-5495.0000246
2021-02-10
Journal of Cold Regions Engineering
Abstract:Frost jacking of electricity transmission tower (ETT) pile foundations in permafrost regions of the Qinghai–Tibet Plateau is becoming increasingly serious. This study investigated the effects of thermosyphons on the frost jacking characteristics of such pile foundations. Field tests of pile foundations with and without thermosyphons were carried out in the Wonkhu–Budongquan section of the Qinghai–Tibet Plateau. A three-dimensional finite-element model was established to analyze the effectiveness of thermosyphons, ground temperature distributions, and jacking displacements and force characteristics of ETT pile foundations. The results showed that the power of thermosyphons decreases yearly within 30 years. The thermosyphons can effectively increase the cold reserves of the permafrost and reduce the soil temperature; the soil temperature around the pile and the depth of thaw is the lowest in the fifth year, and this will increase the top of permafrost by 48 cm in the thirtieth year. Thermosyphons can effectively increase the adfreezing force of the pile side below the active layer and reduce the frost jacking displacement, thus alleviating frost jacking damage to ETT pile foundations.