Research on Alarming Instrument and Master Station for Gateway Energy Measuring Failures
Shuai YANG,Xiang-qun CHEN,Dan ZHAO,Zheng XU,Xiao-qian XIE,Ding-ying GUO,Fang YANG,Can-hui ZHANG
DOI: https://doi.org/10.3969/j.issn.1001-1390.2014.13.005
2014-01-01
Abstract:To deal with the frequent failures of provincial gateway measurement in recent years,this paper develops the measurement monitoring and alarming system with specific software and hardware implementation. By extending the 102 communication protocol,this system uses the failure monitoring terminal to collect events such as voltage lose, current lose,TV failure and power imbalance in real time,and transmits them to master station through PSTN or LAN. These events are used for failure verification with EMS / SCADA and the electrical energy acquisition system in-formation. By means of SMA massage,IMAP mail and online warning,the system reminds OAM staff of processing the information in time. Furthermore,a multi - electricity compensation technique is introduced. Electricity compen-sation formula is automatically generated according to different types of failures,and the compensated electricity will be verified and compensated by balance measures such as the electricity of the busbar,the 3 - side electricity of the main transformer and the electricity of the opposite wires.