High Impedance Fault Detection in Distribution Network Using Convolutional Neural Network Based on Distribution-Level PMU Data

Yongjie Zhang,Xiaojun Wang,Yiping Luo,Jinghan He,Bin Hua,Qin Xu
DOI: https://doi.org/10.1049/cp.2019.0325
2019-01-01
Abstract:High impedance faults (HIFs) have become a serious challenge of distribution networks which are difficult to be detected by the traditional protection scheme. And the access of distributed generations (DGs) makes the fault description more difficult. With the development of distribution-level phasor measurement units (D-PMUs), visual and precise synchronous data could be used for distribution network. In this paper, a Convolutional Neural Network (CNN) based HIF detection method is proposed. The extracted synchronous transient HIF characteristics of decomposed the zero sequence current by wavelet transform is used as the input feature of CNN model. Considering the particularity of fault detection, some of targeted improvement is adopted, which includes local response normalization (LRN) and L2 regularization among multiple optimizations. The proposed HIF detection method is robust to the noise, disturbance, and time window. The performance had been tested on a 20-node distribution network with DGs in PSCAD, where the accuracy rate can reach 97% and the anti-interference capacity and effectiveness was justified from multi aspects.
What problem does this paper attempt to address?