Reduced-Scale Numerical Study on the Effects of Radiant Floor Heating Integrated with Natural Ventilation on Indoor Flow and Dispersion

Peng-Yi Cui,Jia-Qi Wang,Feng Yang,Yuandong Huang,Yong Yang,Wenquan Tao
DOI: https://doi.org/10.2139/ssrn.4220934
2022-01-01
SSRN Electronic Journal
Abstract:Few studies on the characteristics of flow and dispersion caused by indoor radiant floor heating integrated with natural ventilation have been conducted yet. This study employed the reduced-scale numerical models validated by wind-tunnel experiments to investigate the influence of radiant floor heating integrated with natural ventilation on airflow, heat transfer and pollutant dispersion within an isolated building. The Richardson number (Ri) was specified to characterize the interaction between the inflow inertia force and buoyancy force caused by radiant floor heating. Several Ri cases from 0 to 26.65 coupled with cross or single-sided ventilation were considered. Model validation shows that the numerical model coupled with RNG k-ε model can better predict the indoor buoyant flow and pollutant dispersion. Results show that tThis study has guiding significance for indoor radiant floor heating coupled with natural ventilation to improve indoor air quality in winter.
What problem does this paper attempt to address?