Investigation on the Cooling Performance of a Buoyancy Driven Earth-Air Heat Exchanger System and the Impact on Indoor Thermal Environment

Tianhe Long,Yongcai Li,Wuyan Li,Shuli Liu,Jun Lu,Dimeng Zheng,Kai Ye,Zhenyong Qiao,Sheng Huang
DOI: https://doi.org/10.1016/j.applthermaleng.2022.118148
IF: 6.4
2022-01-01
Applied Thermal Engineering
Abstract:The feasibility and cooling performance of a pure buoyancy-driven earth-air heat exchanger system (B-EAHE) with the assistance of combined effect of solar chimney and thermal mass were verified and revealed by a full-scale experimental study. The experimental results showed that the EAHE pipe diameter plays an important role in the system performance, and the airflow rates reach peak values of approximately 252 m(3)/h and 166 m(3)/h for the EAHE pipes with diameters of 0.3 m and 0.2 m, respectively. The air temperature differences between the inlet and outlet of the EAHE were approximately 12.5 ?degrees C and 13.0 ?degrees C in maximum, and 4.8 ?degrees C and 4.78 (?)degrees C in average for the EAHE pipes with diameters of 0.2 and 0.3 m. In addition, the amplitude of indoor air temperature was further attenuated under the regulation of the B-EAHE system. The air temperature inside reference chamber varies from 28.3 to 35.1 ?degrees C, while the air temperature inside test chamber with 0.3 m diameter pipe ranges from 28.5 to 30 ?degrees C, which is approximately 2 ?degrees C lower than that for test chamber with 0.2 m diameter pipe. Moreover, higher energy saving potential is justified by the 0.3 m diameter pipe with peak cooling capacity of 1179 W compared with the 0.2 m diameter pipe with peak cooling capacity of 629 W. It is concluded that the B-EAHE system is able to achieve 24 h periodically fluctuating natural ventilation and passive cooling, and to improve the indoor thermal environment greatly in hot summer conditions.
What problem does this paper attempt to address?