Coordinated Emergency Control Strategy for Transient Stability Enhancement of AC/DC Hybrid Power Systems Based on EEAC Theory

Zheng Shi,Yin Xu,Xiangyu Wu,Jinghan He,Hongming Shen
DOI: https://doi.org/10.1109/cieec.2018.8745972
2018-01-01
Abstract:High voltage direct current (HVDC) technology has become an important solution for the interconnection of large-scale power grids. The AC/DC hybrid grid is gradually becoming an important pattern of the modern power grid. Based on the extended equal area criterion (EEAC) theory, this paper presents a coordinated emergency control strategy combining HVDC emergency control and generator tripping to enhance the transient stability of AC/DC hybrid power systems. Firstly, when the fault occurs, the generators are divided into two clusters and then equivalent to a single machine. Subsequently, by fitting the electromagnetic power curve after fault clearance, the equal area rule is used for quantitative analysis to determine the control quantity of HVDC emergency control and generator tripping. Finally, time-domain simulation results provided by PSCAD/EMTDC are used to validate the effectiveness of the proposed method.
What problem does this paper attempt to address?