Improved Generalized S-transform Algorithm for Power Quality Disturbances Analysis and Its Implementation
Jun LIU,Chun HUANG,Yaqun JIANG,Caihong ZHU
DOI: https://doi.org/10.3969/j.issn.1003-8930.2017.03.006
2017-01-01
Abstract:As the power quality disturbances analysis based on traditional generalized S-transform (GST) is of large amount of calculation,it is not conductive to the real time detection and classification of signals.Moreover,and there exist problems including low precision detection and low classification accuracy when the signal-to-noise ratio is not higher enough.In this paper,the traditional GST algorithm is improved and applied to the analysis of power quality disturbances.Firstly,fast Fourier transform is used to estimate signal frequency,narrow the range of frequency domain analysis,and saves the computation time obviously.Secondly,considering that the disturbance amplitude curve changes slowly at the start and stop time when using the traditional S transform,bi-gaussian window is used instead of traditional Gaussian window,and an adaptive parameter selection window function is used to obtain the analog matrix information more reliably after transformation.Finally,with the aid of MatlabR2010b simulation platform,a new index is introduced to accurately estimate the start and stop time information of disturbances,extract effective features to conduct classification directly,or identify particular disturbances by means of simple discrimination tree,which improves the efficiency and accuracy of classification.Through the analysis results of 12 kinds of power quality disturbance signals,the effectiveness of the proposed method is verified.