Stability Analysis of Electrical Oscillation Existing in Grid Integration of PMSG-based Wind Farm with VSC-HVDC System

Kun Sun,Wei Yao,Jinyu Wen
DOI: https://doi.org/10.1049/cp.2019.0512
2019-01-01
Abstract:Compared with the traditional sub/super-synchronous oscillation in grid-connected permanent magnet synchronous generator (PMSG)-based wind farm, a new type of electrical oscillation which over the super-synchronous frequency region may also occur in the grid integration of PMSGs through voltage source converter based HVDC (VSC-HVDC) system, which is worthy of further study. In this paper, the positive sequence impedance models both of PMSG-based wind farm and the wind farm VSC (WFVSC) station are established. Then the equivalent impedance model of the whole system can be further represented. The analysis results show that PMSG represents as a negative resistance in series with a capacitance at the resonant frequency point, while WFVSC represents as a resistance-inductance. Thus, the electrical oscillation tends to appear due to the negative damping effect of PMSG. Furthermore, this paper studies the influence of PI controllers' parameters of grid-side converter (GSC) of PMSG and WFVSC on the characteristics of the oscillation. In addition, the impact of the operating condition such as the output power level of PMSG on the oscillation characteristics are analysed as well. Finally, the correctness of the analysis results is validated by time-domain simulation.
What problem does this paper attempt to address?