Experimental Investigation of a Ground Source Heat Pump Based Snow Melting System: Control Optimization

Wenke Zhao,Yaning Zhang,Lei Li,Wentao Su,Bingxi Li,Zhongbin Fu
DOI: https://doi.org/10.1007/978-3-030-38804-1_14
2020-01-01
Abstract:A snow melting system based on a ground source heat pump was implemented in Harbin, the coldest provincial capital of China. Two control methods (automatic on/off and variable frequency) were applied to investigate the performances of the snow melting system. Two continuous operations were conducted for 4 h which is the time for the snow melting. The ambient temperatures, the temperatures of supplied water and the energy analysis (COP, coefficient of performance) of the snow melting system were detailed. The results indicate that the variable frequency control method can supply more steady hot water (the maximum error values and accuracies were decreased by 63.9% and 64.2%, respectively) and it has higher energy efficiency (the average COPsys and COPhp were increased by 19.8% and 56.8%, respectively) as compared with the automatic on/off control method.