Analysis of Common Mode Voltage and Current in MMC Flexible DC System with AC Side Grounding Method

Jing Wang,Wenkang Qin,Yuming Zhao,Xinsen Xu,Xidong Xu
DOI: https://doi.org/10.1109/icpes51309.2020.9349686
2020-01-01
Abstract:Employing the third harmonic injection modulation method can improve the DC voltage utilization rate for MMC. The third harmonic injection will generate the third common-mode voltage at the DC side of the MMC-based DC distribution network. This paper analyzes the MMC of three harmonic voltage. A common-mode equivalent network model of a multi-terminal DC distribution network is established. When the neutral grounding mode on ac side is adopted in the multi-terminal DC distribution network, the equation between neutral grounding impedance and common-mode current and voltage is derived. Finally, it is verified on the PSCAD simulation program.