Voltage-frequency Coupled Transient Instability Analysis of the Weak Grid-Connected DFIG-based Wind Plant During LVRT

Jinxin Pei,Jun Yao,Peng Sun,Yuan Liu
DOI: https://doi.org/10.1049/cp.2019.0296
2019-01-01
Abstract:With the rapid increase of the wind plant (WP) injection, the interaction between the WP's output current and the transmission line's impedance will affect the terminal voltage as well as the phase-locked loop (PLL) output value at the same time. The new shapes of the transient instability issues of the large-scale doubly fed induction generator (DFIG)-based wind plant during low voltage ride through (LVRT) must be noted. In this paper, the transient equivalent model of WP based on grid code is established firstly. On this basis, the voltage-frequency coupled transient instability phenomenon of the DFIG-based wind turbines (WTs) during LVRT is investigated. Moreover, the major influencing factors which resulting in the instability risk were identified, including voltage dips degree, operating conditions, and the transmission distance. Finally, the simulation for the DFIG-based WT system is carried out using Matlab/Simulink, and the simulation results are presented to verify the correctness of the theoretical analysis.
What problem does this paper attempt to address?