PD Positioning of Electrical Transformers Based on the Designed Pressure-balanced EFPI Sensor Array

Yingjie Xi,Chuanxian Luo,Xu Yang,Chongxing Zhang,Ming Dong,Yang Liu
DOI: https://doi.org/10.1109/eic49891.2021.9612271
2021-01-01
Abstract:Extrinsic Fabry-Perot interferometric (EFPI) fiber-optic ultrasonic sensor, for its advantages, has been widely concerned in partial discharge (PD) detection. In this paper, a novel structure of EFPI sensor is proposed to achieve built-in detection in power transformers. A unique sensor array and installation position are specially designed for built-in detection. Based on the sensor array, steered response power (SRP) algorithm and time difference of arrival (TDOA) algorithm are combined to give a more accurate positioning result. The experimental result shows good positioning accuracy, which illustrates the feasibility of the designed sensor array and optimized algorithm.
What problem does this paper attempt to address?