Indoor Air Quality Investigation At University Dining Halls In Wuhan

Xiaojiang Ye,Huanxin Chen,Liangyan Lu,Zhaoxia Zhou,Zhao Wang,Genping Wu,Zhiwei Lian
2007-01-01
Abstract:Nine dining halls in the six universities were selected for this study to survey the indoor air quality in dining halls in Wuhan. The indoor air pollutants that included PM10 (particulate matters with 10 aerodynamic diameters less than 10 um), carbon monoxide (CO) and carbon dioxide (CO2) were measured. The results indicated that the dominance sources were indoor sources such as cooking, tobacco smoking and human exhausts in the university dining halls. The outdoor sources such as vehicle exhausts were subordinate sources. PM10 level in most dining halls, more than 67%, was higher than the standard of Chinese indoor air quality. The maximum indoor PM10 level in this study reached 0.694 mg/m(3). Poor ventilation system also had effect on the air quality in the dining halls. The CO level could reach 14.4 ppm in the dining hall without good ventilation.