Abstract:Criteria which stipulate the minimum pressure at which water is to be delivered to customers from a water distribution system (WDS) differ around the world. Thus, interestingly, the pressure delivered to a customer might be judged high enough to meet standards in some countries, while water delivered under the same pressure in other countries is considered unacceptable. This paper provides a description of consequences and implications of changes in the minimum pressure criterion (MPC) to WDS design. Reducing the MPC may cause a decrease in pressure-based demands such as faucet, showers, and lawn watering and also improve system performance through reduced energy use, leakage, and the frequency of pipe breaks. However, lowering this criterion may make the system more susceptible to low pressure failures, either hydraulic (e.g., an inability to supply the required flow) or safety related (e.g., increasing the risk of an intrusion event associated with hydraulic transients). Therefore, there should be a clear understanding of the consequences and challenges prior to changes the MPC. Moreover, policies to control and avoid low pressure events are seldom fully linked to the value of the minimum pressure standard and the issue how the MPC is enforced/ensured in WDSs. The inter-related issues associated with MPC are raised here as important but neglected issues.