Abstract:A seated computational thermal manikin with geometry of a real human body is used to investigate the personalized ventilation efficiency and human exposure in a displacement and mixing ventilated room. The air velocity, temperature, and contaminant concentration field indoor are simulated by RNG k-epsilon model including low Reynolds number effect. The modeling outcome indicates that the performance of personalized ventilation is sensitive to the room air distribution method due to the weak jet flow of personalized air since its flow rate is limited by the thermal comfort. The thermal plume around the human body plays a key role in determining the inhaled air quality. Human exposure with personalized ventilation is dominated by the fraction of personalized air in the inhaled air and the contaminant concentration in the ambient room air. Generally the application of personalized ventilation is able to improve the inhaled air quality greatly.