Optimal Distribution of Active Power for Tie-Lines in Long-Distance AC/DC Parallel Transmission Channel
Wen-tian LU,Shun-jiang LIN,Ming-bo LIU
DOI: https://doi.org/10.3969/j.issn.1000-565X.2017.07.003
2017-01-01
Abstract:According to the hierarchical and zoned dispatching characteristics of multi-area interconnected AC/DC power systems, an optimal distribution method of active power for tie-lines in long-distance AC/DC parallel trans-mission channel is proposed on the basis of a given total power exchange schedule among regions. In the optimiza-tion model, the minimum active power loss of AC/DC tie-lines is used as the objective function, and, security con-straints of the inter-province AC tie-line sections, as well as the constraints of power regulation range and regulation frequency limit of DC tie-lines, are taken into consideration. Then, a power transmission schedule of AC/DC chan-nels is obtained. Instead of DC power flow model, a practical model called simplified AC power flow model is pro-posed, which is used to calculate the transmission power of inter-province AC tie-lines with hundreds of kilometers in length more accurately. Moreover, for the purpose of satisfying the constraints of DC tie-line power regulation frequency limit and the minimum duration limit of each power state of DC tie-lines, an improved three-stage method is applied to the optimization model. Thus, the optimization model can be decoupled in each dispatch period, and each sub-model can be parallelly computed in each dispatch period. Finally, by taking a practical large-scale AC/DC interconnected multi-area power system for example, the correctness and effectiveness of the proposed optimiza-tion model and the corresponding solving algorithm are both verified.