Fast Identification of Inside and Outside Faults of HVDC Based on Frequency Spectrum Characteristics

LI Cong-shan,LIU Tian-qi,LI Xing-yuan,HE Ping,JIN Nan
DOI: https://doi.org/10.3969/j.issn.1001-0548.2017.06.014
2017-01-01
Abstract:Fast identification of internal and external faults of high voltage direct current (HVDC) is the basis of protection. Due to the influence of direct current (DC) filter, smoothing reactor and line distribution capacitance, there exists a big difference of physical boundary which the DC current transmits through to the relay location when internal and external faults occur. Therefore, the energy distribution of DC current frequency band is obviously different. In this paper, the DC current signals are decomposed by the ensemble empirical mode decomposition (EEMD) method, and the signals are decomposed into the sum of several intrinsic mode components (IMF). Then, the energy of each modal component is calculated. By comparing and analyzing, the distinguishing features are identified, and then the energy ratio index is defined to distinguish the normal, internal fault, external fault on both sides. This method only uses the DC current signal, which is easy to implement, and can meet the requirements of rapidity and selectivity. Finally, the simulation and analysis of a large number of faults in HVDC under various operating conditions verify the effectiveness and robustness of the proposed method.
What problem does this paper attempt to address?