PCA-SVDD-based chiller fault detection method

Guannan Li,Yunpeng Hu,Huanxin Chen,Haorong Li
DOI: https://doi.org/10.13245/j.hust.150825
2015-01-01
Abstract:A PCA (principal component analysis )‐SVDD (support vector data description )‐based method was presented for chiller fault detection .First ,chiller fault‐free operating data were decom‐posed into two subspaces ,i .e .principle component subspace (PCs) and residual subspace (Rs) ac‐cording to the PCA method ,and then a SVDD model was developed based on the residual score matrix to detect chiller faults .Chiller experimental data from RP‐1043 were exploited to validate the PCA‐SVDD‐based method ,and the PCA‐SVDD‐based chiller fault detection results were compared with those obtained by conventional PCA‐based and SVDD‐based methods .Results show that the PCA‐SVDD‐based method can be used for chiller fault detection ,and most of its fault detection results are better than those of PCA‐based and SVDD‐based method ,especially on lower fault severity level , w hich is conducive to early fault detection and reduce the loss .
What problem does this paper attempt to address?