An Evaluation Method of Annual Energy Consumption of Chilled Water Pumps Group Based on Suboptimal Solutions

Jin-ping Liu,Zhi-tao Lu,Xue-feng Liu,Kong-zu Xing,Yue-bang Mai
DOI: https://doi.org/10.3969/j.issn.1000-565X.2015.07.015
2015-01-01
Abstract:Proposed in this paper is an evaluation method of energy consumption suboptimization with chilled water pump group, and according to this evaluation method , an optimized random step optimization method is used to op-timize the design of the model in pumps group .Then, the influences of control pressure difference and rated flow on annual energy consumption characteristics are analyzed by an example , and different frequency conversion control modes are compared .The results show that (1) the optimized random step optimization method performs better in coping with locally-optimal and convergent problems than traditional optimization methods do ;(2) the annual total energy consumption differences caused by different load rate distribution can reach more than 50%, so the annual load distribution must be taken into account in the energy consumption evaluation of system ;(3) the system of big-ger bypass pressure and lower rated flow has wider low and middle energy regions , its energy consumption under different load rate limits is far away from the lowest energy consumption and the corresponding energy consumption evaluation is more tolerant;and (4) in most cases, adopting synchronous frequency conversion control becomes ad-vantageous with the increase of flow or control bypass pressure rating .