Aseismic control of transmission towers with nonlinear suspended mass pendulums

Jie HOU,Lin-sheng HUO,Hong-nan LI
DOI: https://doi.org/10.3969/j.issn.1000-3835.2014.03.033
2014-01-01
Abstract:Due to the limitation of linear analysis for a suspended pendulum control system with small swing angle, a method analyzing dynamic response of a structure considering nonlinear stiffness of pendulum was proposed here.Taking a 500 kV transmission tower as a numerical example and comparing the results under linear and nonlinear conditions,it was found that the swing angle of pendulum may exceed the limitation of linear assumption and the nonlinear analysis can simulate a structural dynamic system with large swing angles of pendulum perfectly.The effects of parameters of the control system including excitation periods,pendulum length and mass ratio on the seismic reduction ratio of the transmission tower were studied.Three seismic records were used to calculate the dynamic response of the transmission tower with suspended pendulums.The results showed that the mitigation effect of suspended pendulums on the structural response is very obvious under different seismic excitations.
What problem does this paper attempt to address?