Numerical Study on the Heat and Mass Transfer of LiBr/H2 O Falling Film Absorption with Low Reynolds Number

Lianying Zhang,Yang Li,Yuan Wang,Xiaohu Yang,Liwen Jin,Xiangzhao Meng
DOI: https://doi.org/10.3969/j.issn.0253-4339.2017.06.020
2017-01-01
Abstract:LiBr/H2 O falling?film absorption is a common heat?and mass?transfer process in an absorption air?conditioning system. By ana?lyzing the coupled heat and mass transfer of the falling?film absorption process, two?dimensional physical and mathematical models of the falling?film absorption along a vertical wall were established. The model was solved using the Fluent computational?fluid?dynamics soft?ware. The interfacial temperature, the concentration profile across the falling film, and the average heat?and mass?transfer fluxes and coef?ficients were obtained. The effect of the Reynolds number on the heat and mass transfer of the falling film was investigated. The results show that, when the film Reynolds number is less than 150, the average interfacial temperature increases with the increasing Reynolds number;however, the rising trend of the average interfacial temperature is more and more gentle. The average mass?transfer coefficient in?creases with the increasing Reynolds number, while the average heat?transfer coefficient decreases. Simultaneously, with the increasing Reynolds number, the average heat?and mass?transfer fluxes first increase and then decrease. An optimal Reynolds number exists that leads to the maximum heat?and mass?transfer fluxes. The average heat?and mass?transfer fluxes reach their maximums, 7. 2 kW/m2 and 2. 9 × 10 -3 kg/(m2·s), respectively, when the Reynolds number is 50.
What problem does this paper attempt to address?