Theoretical Study of the Optimal Proportion of Non-azeotropic Refrigerant Mixtures of R32 and R123

Jifeng Shangguan,Guoyuan Ma,Shuxue Xu
DOI: https://doi.org/10.3969/j.issn.1671-6612.2015.03.020
2015-01-01
Abstract:Based on the principle of complementary advantages of mixed refrigerants, this paper proposed binary zeotropic refrigerant mixtures of R32 and R123. Matlab is used for theoretical circular calculation of the mixture at different proportion by calling property parameters from Refprop developed by NIST. By comparasion of performance parameters under 5 different conditions in the single compression system, the result indicates that, after adding 5~7 percent R32 to pure R123 under the second and fourth conditions, the coefficient of performance(COP) of the mixed refrigerant can increase 38.08%~52.94%, significantly increasing the system pressure. After adding 10 percent R123 to R32 under the 5th condition, theCOP of the mixed refrigerant can increase 6.4%, the discharge temperature decreases 3.2℃, TheGWP can be reduced by 8.22%.