Scheme for Transformer Backup Protection Using Substation-area Information in Smart Substation

FAN Zhanfeng,LIU Xing,LIU Yiqing,GAO Houlei,SONG Guobing,DENG Maojun
DOI: https://doi.org/10.7500/AEPS20170406008
2017-01-01
Abstract:For defects in the transformer backup protection based on the over-current principle and compound voltage blocking such as insufficient sensitivity,complicated cooperation and long fault clearing time-delay,a transformer protection scheme is proposed with the main protection separated from the backup protection in the smart substation.The independent backup protection employs the directional comparison principle to locate the fault position by the substation-area shared information.The backup protection provides the protective functions for transformer inner faults,medium-and low-voltage bus-bar faults,dead-zone faults and the situation where the breaker refuses to act.The negative-sequence directional element and zero-sequence directional element are used to reflect unbalanced faults,and the directional element by comparing the amplitude and phase of positive-sequence current is used to reflect the three-phase fault.A typical 110 kV substation is established in PSCAD to facilitate simulation of various types of faults.
What problem does this paper attempt to address?