Mechanism Analysis of Virtual Power Angle Stability in Droop-controlled Inverters

HUANG Linbin,ZHANG Leiqi,XIN Huanhai,HU Jiabing,GAN Deqiang
DOI: https://doi.org/10.7500/AEPS20150709007
2016-01-01
Abstract:Under a large disturbance,similar to synchronous generators (SGs),the transient instability may occur on the voltage-source-type droop-controlled inverters. Moreover, the inverter will turn into a current source since its current saturates,resulting in a more complicated synchronous stability problem.This paper studies on the single-inverter infinite-bus system.The virtual power angle is defined to obtain the virtual power angle characteristics with and without current saturation, which is used to analyze the synchronous stability mechanism of the inverter as well as the instability process.The influences of the fault-clearing time on the virtual power angle stability are also analyzed.And this method is extended to the transient stability analysis of the virtual synchronous machine.Finally,the rationality of the instability analysis method is verified via simulations under MATLAB/Simulink.
What problem does this paper attempt to address?