Coordinated Control Strategy of Offshore Wind Farms and VSC-based HVDC Transmission Systems

HONGMin,XIN Huanhai,XUChenbo,ZHANGLeiqi,GAN Deqiang
DOI: https://doi.org/10.7500/AEPS20160418015
2016-01-01
Abstract:A novel coordinated control strategy for wind farms based on offshore doubly-fed induction generator (DFIG) type integrated into voltage source converter based (VSC-based) high voltage direct current (HVDC) transmission system is proposed.The constant power control strategy based on phase locking loop (PLL) is applied to the sending converter station, which regulates the active power according to the reference from the wind farm.Meanwhile,the droop of the active power and the squared DC voltage is added to active power control loop of the sending converter station to enhance the transient stability of the DC voltage.The synchronized control is applied to the offshore DFIG wind turbines,which can control the amplitude and angle for the offshore AC grid voltage.Compared with the classical fault ride-through(FRT)coordinated control strategy,this novel control strategy can enhance the DC voltage transient stability and is insensitive to communication delay.Meanwhile,the novel control strategy can also achieve low-voltage ride-through in the case of a 3-phase short-circuit at the sending converter station.This paper uses the example of an offshore wind farm integrated into a two-terminal multilevel modular converter (MMC) VSC-based HVDC transmission system as simulation cases to validate the effectiveness and advantages of the novel FRT coordinated control strategy.
What problem does this paper attempt to address?