Effect of High Frequency Impulse Voltage Upon Dielectric Response of XLPE Cables

Jiankang ZHENG,Aixuan ZHAO,Tao LIN,Long XU,Linzi ZHENG,Junbo DENG,Guanjun ZHANG
DOI: https://doi.org/10.3969/j.issn.1673-7598.2018.05.008
2018-01-01
Abstract:The widely-used power cable will withstand certain overvoltage. In the actual operation, the cable intermediate joints explosion resulted from overvoltage is often encountered,which seriously affects the safe and stable operation of power system.In order to study the influence of high frequency part of operating over-voltage upon cable insulation condition, the typical types of cable intermediate joint is selected as research object,and carries on the slice.For these aged cable samples,dielectric response are used to analyze the change of cable insulation parameters,and Fourier transform infrared spectroscopy(FTIR)are used to verify the results. The test results show that the impulse aging of XLPE promotes the decomposition of crosslinking agent DCP and the increase of impurity particles caused by the interface,which could produce potential breakdown channels.Therefore,it is important to pay attention to high frequency surge insulation effect on cable and strengthen technical supervision measures for avoiding the breakdown.
What problem does this paper attempt to address?