Effect of Open-Phase in Input Terminal on Auto-Connected 12-Pulse Rectifier

GAO Lei,MENG Fan-gang,QIN Xiao-bo,YANG Shi-yan,YANG Wei
DOI: https://doi.org/10.15938/j.emc.2016.08.004
2016-01-01
Abstract:The effect of open-phase on 12-pulse rectifier using step-up delta-connected autotransformer was analyzed, and the voltage and current characteristic of 12-pulse rectifier under normal operation and open phasing were presented, respectively.Theoretical analysis and experimental results show that the in-stantaneous difference of the two bridge rectifiers’ output voltages is the key point of realizing 12-pulse rectification.After open phase, the 12-pulse rectifier is equivalent to be two single-phase rectifiers with the equal input voltages which means that the instantaneous voltage difference is zero, causes the load voltage to be 2 pules, and depresses the power quality of DC side.Input line current of the phase under open phase is zero, which causes the rectifier operates to be at asymmetrical condition.The results pro-vide the basis of analysis and real time processing for parallel-connected 12-pulse rectifier under open-phase.