Research on FuII Waveform Bus Protection Based on the OpticaI Current Transformer
Zhibin Ouyang,Guoqing Zhang,Jinming Ge,Wenhui Zhou,Lei Chu,Cui Yang,Yue Chen
DOI: https://doi.org/10.3969/j.issn.1000-3886.2019.06.017
2019-01-01
Abstract:Bus, an important part of the power transmission and distribution network, plays the role of convergence and distribution of electric energy.As the electromagnetic current transformer cannot measure non-periodic components accurately and has the problem of magnetic saturation, bus protection operation takes a long time, and false operation sometimes happens.A new bus protection criterion using full waveform information was proposed to improve the performance of protection actions.According to the new criterion, judgment was made at the sampling points within 1/4 cycle on the basis of fault full-waveform data collected by the optical current transformer, so that the operation time was reduced to a minimum under no affection of magnetic saturation.Setting analysis was made on the protection fixed value.A bus system model was established on the Simulink platform.Simulation verified that the protection operation time of the new type of bus was significantly reduced as compared with traditional protection, and operation reliability was also improved.Finally, the influence of harmonics on the new criterion was analyzed to ensure the feasibility of the criterion.