Adaptive Novel Feed-forward Control Strategy for LCL Type Grid-connected Inverters in the Weak Grid
Ziheng CAO,Xianyong XIAO,Yuan LI,Daijun LUO,Hangya WANG,Yang ZHOU
DOI: https://doi.org/10.13336/j.1003-6520.hve.20200515010
2020-01-01
Abstract:The traditional proportion feed-forward strategy can greatly restrain disturbances from harmonics of grid background, but in a weak grid, due to the existence of grid impedance, positive feedback channel and grid-connected current inner-loop are coupling with each other by grid impedance, thus robustness substantially decreases. According to the above situation, a kind of adaptive novel feed-forward control strategy based on grid impedance measurements is proposed. Firstly, a multi-resonance link is added on the positive feedback channel of the voltage for common coupling point, thus the positive feedback channel has a feedback effect only at the frequency of main grid background harmonics, so that its robustness can be improved and the harmonic suppression ability of proportional feed-forward strategy can be remained to a certain extent. However, the improvement of robustness has some limitations after promotion, so an adaptive link is added to adjust open-loop gain in real time for further improvement of robustness. In the end, the control strategy is verified through the simulation. The simulation results show that the proposed strategy can make the LCL type grid-connected inverters always have good robustness under weak grid condition.
What problem does this paper attempt to address?