AC Breakdown Characteristics of CF3I-N2 Gas Mixtures in Condition of Quasi-homogeneous and Extremely Non-uniform Electric Field

Yunkun DENG,yi MA,Xianfu CHEN,Shaoquan ZHANG,Xiaoyun CHEN,Dengming XIAO
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170303009
2017-01-01
Abstract:Trifluoroiodomethane (CF3I) has been broadly proposed as a potential replacement for SF6.AC breakdown tests on CF3I-N2 gas mixtures have been completed in the condition of quasi-homogeneous and extremely non-uniform electric field,focusing on the CF3I-N2 gas mixtures with volume fraction of 20% and 30% CF3I,gas pressure from 0.1 MPa to 0.3 MPa,and gap distance from 5 mm to 30 mm.On the basis of the foregoing analyses of breakdown characteristics,we reveal the effect laws of CF3I volume fraction,gap distance,gas pressure,and electric field non-uniform coefficient on the power frequency breakdown voltage of CF3I gas mixtures.The AC breakdown voltages of CF3I-N2 gas mixtures linearly increase with the gas pressure and gap distance under quasi-homogeneous field.In the condition of non-uniform field,the AC breakdown voltages of CF3I-N2 gas mixtures approach to saturation with the increasing of gas pressure.The experimental results indicate that CF3I-N2 gas mixtures with CF3I volume fraction of 20% and 30% can achieve nearly 50% and 55% power frequency withstand voltage of pure SF6,respectively.
What problem does this paper attempt to address?