Partial Discharge Detection Technology Based on the Fibre Bragg Grating

YE Haifeng,QIAN Yong,LIU Yadong,LIU Zongjie,CHEN Ruilong,JIANG Xiuchen
DOI: https://doi.org/10.7158/e13-097.2014.11.2
2014-01-01
Australian Journal of Electrical & Electronics Engineering
Abstract:In this study, the application conditions and influential factors of fibre Bragg grating sensors used for partial discharge detection are analysed by discussing basic mechanics of fibre Bragg grating sensors. A partial discharge detection system based on a fibre Bragg grating sensor is designed and used for detection of free metal particle discharge and suspended metal electrode discharge in oil. The detection results are compared with that of a system based on a piezoelectric sensor in comparison tests. The comparison includes the detection sensitivity, anti-vibration ability, and ability against strong electromagnetic interference in substations. The test results show that the system based on the fibre Bragg grating sensor can effectively detect typical discharges; its sensitivity is similar to that of the system based on the piezoelectric sensor. The fibre Bragg grating system is more easily interfered by vibrations, but has greater anti-electromagnetic interference ability than the piezoelectric system.
What problem does this paper attempt to address?