Abstract:The widely used phasor measurement units (PMU), one of the most important techniques of smart grids, offer a data platform for power grid dynamic security measurement and control. Whether the PMU can accurately track the primary signal of power systems under the dynamic condition becomes crucial. However, under the dynamic condition, the traditional discrete Fourier transform (DFT) leads to error because of the spectral leakage, which causes blunder of the oscillation analysis. Besides, the spectral aliasing accrues when the phasor measurements are reported to the main station, which can interferes the security control applications. In this paper, the arrangement of filter in PMU was discussed. The phenomenon of spectral leakage and aliasing under dynamic states were revealed and the improvements brought by the digital filter were proved. Moreover, how the setting up of the digital filters influents the applications was certified. The computer simulation results demonstrated the above theoretical analysis.