Ageing Condition Assessment of XLPE Cable Insulation Based on tanδ at 0.1 Hz

Ying Liu,Linjie Wang,Yu Su,Yang Xiao,Xiaolong Cao
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2016.05.009
2016-01-01
Abstract:The detection technology of XLPE cable insulation has recieved more and more attention with the continuous development of power cable industry. It is an important and indispensable process of elec-trical equipment management at present for the effective assessment of cable insulation ageing condition. According to the IEEE test criteria about cable insulation diagnosis method at very low frequency (0.1 Hz), a new method was put forwarded to assess the ageing condition of XLPE insulation. The sam-ples were sliced from XLPE cable insulation layer, and the tanδ of the slice samples at 0.1 Hz were tested under different voltages, and then the voltage sensitivity was used to judge the ageing dgree of insulation. It is found that the change rule of tanδ with voltage can effectively reflect the difference of insulation ageing condition for the power cables after operating different years, and the tanδ of inner, middle, and outer insulation layers is different. The tanδ of inner and middel layers is normalized by set-ting the tanδ of outer layer as reference, and the relative value is used as a judgement basis of insula-tion ageing state. This method is an effective way for ageing condition assessment of XLPE cable insula-tions which are lack of original data.