Experiments of Feasibility of Hydrocyclone Anti-blockage Device

Long Ni,Jin-yi Tian,Jia-ning Zhao,Yang Yao
DOI: https://doi.org/10.3969/j.issn.1001-523X.2016.10.006
2016-01-01
Abstract:To solve the blockage issues and relieve the fouling problems of the sewage heat exchanger in the sewage source heat pump, the hydrocyclone anti-blockage device was proposed. Under the combining effect of the continuous underlfow and overlfow relfux, the foulant could be removed temporarily and the heat could be taken from the sewage after decontamination. In addition, the feasibility test rig was built up and the feasibility experiments of sand-water, high-concentration sewage and low-concentration sewage were conducted, respectively. Furthermore, the experimental results illustrated that the hydrocyclone anti-blockage device could separate the foulant efifciently. Maintaining low split ratio, the separation efifciency for sand-water was close to 100%, and the separation efifciency for high-concentration sewage was within 93%~97%, and the separation efifciency for low-concentration sewage was within 57%~72%. The separation efifciency was proportional to the foulant density, whereas it had basically nothing to do with the feed pressure. The energy loss was 10~20 kPa.