Experimental Study on the Performance of Small-sized Cool Storage Air Conditioning with Phase Change Materials

Dongbo WU,Quan ZHANG,Xiaoming CHEN,Shuguang LIAO,Zhengyong SHA
DOI: https://doi.org/10.13614/j.cnki.11-1962/tu.2017.06.10
2017-01-01
Building Science
Abstract:A small-sized cool storage air conditioning with phase change materials working with R22 was developed.The temperature,pressure and input power were measured.The performance of refrigeration circulation at different refrigerant charge in ordinary air conditioning (OAC) mode and cold charging (CC) mode were investigated.The results show that the suction and exhaust pressure in OAC mode both increased gradually as refrigerant charge increased from 1,000 g to 2,200 g;and the pressure in CC mode increased first and then decreased.At the same time,the cooling capacity and COPa in OAC mode and the average cold storage rate and COPs in CC mode both firstly increased and then decreased.When refrigerant charge was 1,600 g,the cooling capacity and COPa reached their maximum simultaneously in OAC mode.But the optimal refrigerant charge in CC mode was 1 200 g.As the refrigerant charge increased from 1,200 g to 1,600 g,the cooling capacity and COPa in OAC mode increased by 4.9% and 4.1%,respectively.Accordingly,the average cold storage rate and COPs in CC mode decreased by 1.7% and 3.2%,respectively.
What problem does this paper attempt to address?