Application Analysis on Night-time Ventilation in Nanjing Area based on EnergyPlus

Xiao-long YUE,Cai-hua LIANG,Xiao-song ZHANG
DOI: https://doi.org/10.3969/j.issn.1003-0344.2014.02.002
2014-01-01
Abstract:In orderto study the feasibility ofnight-tim e ventilation in Nanjing,a typicaloffice building was selected and building energy sim ulation software EnergyPlus was used to sim ulate.In the typicalweather conditions,considered the ventilation tim e,the air change rate and other factors on the indoor tem perature,hum idity,and enthalpy.The change in enthalpy of the indoor air was equivalentto the power consum ption of source heatpum p air-conditioning,by com paring the energy consum ption in fan power consum ption.The results showthat:ventilation tim e appropriate to selectthe tim e when outdoor tem perature is lower. The air change rate corresponds to different critical point in different ventilation tim e.W hen air change rate is less than that of the critical point,the equivalent air-conditioning power consum ption is greater than the fan power consum ption.Ithas energy-saving effect.W hen the ventilation tim e is from 6:00 to 6:30 am , air change rate is 1~2 ac/h, the absolute difference of equivalent air-conditioning power consum ption and fan power consum ption was m axim um ,energy saving reach 3.6kW h in halfan hour.
What problem does this paper attempt to address?