Effect of Separation Distance on Gas Dispersion and Vapor Cloud Explosion in a Storage Tank Farm Determined Using Computational Fluid Dynamics

Qiuhong Wang,Yilin Sun,Chi-Min Shu,Juncheng Jiang,Mingguang Zhang,Qingfeng Wang,Xuefan Wang
DOI: https://doi.org/10.1016/j.jlp.2020.104282
IF: 3.916
2020-01-01
Journal of Loss Prevention in the Process Industries
Abstract:Storage tank separation distance, which considerably affects forestalling and mitigating accident consequences, is principally determined by thermal radiation modeling and meeting industry safety requirements. However, little is known about the influence of separation distance on gas dispersion or gas explosion, which are the most destructive types of accidents in industrial settings. This study evaluated the effect of separation distance on gas dispersion and vapor cloud explosion in a storage tank farm. Experiments were conducted using Flame Acceleration Simulator, an advanced computational fluid dynamics software program. Codes governing the design of separation distances in China and the United States were compared. A series of geometrical models of storage tanks with various separation distances were established. Overall, increasing separation distance led to a substantial reduction in vapor cloud volume and size in most cases. Notably, a 1.0 storage diameter separation distance appeared to be optimal. In terms of vapor cloud explosion, a greater separation distance had a marked effect on mitigating overpressure in gas explosions. Therefore, separation distance merited consideration in the design of storage tanks to prevent gas dispersion and explosion.
What problem does this paper attempt to address?