Experimental investigation on single-phase convection heat transfer in annular gap

RL Liu,GH Su,SZ Qiu,ZH Wang,DN Jia
1999-01-01
Abstract:The forced convection of single-phase water in annular microchannal with 1.0 mm gap has been experimentally investigated. The experimental condition is that inner tube and outer tube are heated simultaneously, the outside diameter of inner tube is 8mm, and the inside diameter of outer tube is 10mm. The results show that the Nusselt numbers for annular gap are smaller than those predicted by Dittus-Boelter formula form. And the Nusselt numbers of inside-wall in annular gap are slightly higher than those of outside-wall. The whole Nusselt numbers of annular gap are greater than those of outside-wall, and smaller than those of inside-wall. The Nusselt numbers for double heated are higher than those of single heated. Reynolds number and Prandtl number range in 463.8 similar to 1528.5 and 0.9 similar to 3.0, respectively. The uncertainty of the experimental data is less than 33%.
What problem does this paper attempt to address?