THERMAL COMFORT AND AIR QUALITY OF UNIVERSITY CLASSROOMS IN WINTER

Xiaojiang Ye,Huanxin Chen,Zhijian Hou,Zhaoxia Zhou,Duanyong Li,Liangyan Lu,Wei Zhou,Qing E
2009-01-01
Abstract:Indoor environmental quality (IEQ) in university has become an important concern for many researchers today. IEQ in classroom was connected with the health and productivity of university students. Air quality in classroom was not only influenced by indoor environmental factors but also influenced by outdoor environmental factors. An investigation was carried in Wuhan to study the indoor thermal environment in university classroom. This study was carried out in winter in 2007. Indoor air temperature, humidity and some indoor air pollutants were measured. The indoor air pollutants included PM10 (particulate matters with 10 aerodynamic diameters less than 10 um), carbon monoxide (CO) and carbon dioxide (CO2). The indoor concentrations of these target air pollutants at classrooms were measured and compared. Moreover, the effects of indoor air temperature on the thermal comfort were also investigated. The accuracy of the instruments followed that prescribed in ASHRAE Standard 55 and ISO 7726. The results showed that air temperature was low and humidity was high in no-heating classroom. The neutral temperature was 21.7 degrees C in classroom during winter. The university studies in classroom preferred slighter thermal environment. All of the measured mean concentrations of PM10 at the classrooms were below the Chinese standard of 150ug/m(3). The change of concentration of CO and CO2 were small. The number of students, air tight of buildings, the opening of windows and doors, etc, had effect on the concentration Of CO2 in classroom.