A NOVEL DIFFERENTIAL PRESSURE OPTIMAL RESET STRATEGY AND ITS APPLICATION IN VWF SYSTEM

Tianyi Zhao,Jili Zhang,Yongpan Chen,Zhen Lu,Liangdong Ma,Dexing Sun
2009-01-01
Abstract:The fixed difference pressure (DP) setpoint (Delta P(SET)) control strategy is adopted as a common control method in practice. Its pump power consumption is generally huge due to its Delta P(SET) IS generally higher than that actually need. Therefore, Delta P(SET) should be continuously reset according to the variation of end user load, which is called variable Delta P(SET) control strategy. In this control method, how to reset Delta P(SET) and what parameter is suitable to be the reference in Delta P(SET) reset are critical issues to be investigated: To solve these problems, this paper focuses on Delta P(SET) reset issues, firstly presents two concepts including worst-case thermodynamic loop and maximum valve position loop, then presents a novel Delta P(SET) reset strategy based on reset domain of valve position in maximum valve position loop, finally applies the Delta P(SET) reset method in a primary pump variable water flow system with DP monitoring point located between water segregator and water collector. Simulation results show that presented optimal strategy performs better integrated evaluation index than other common reset strategies, resetting Delta P(SET) based on valve position in worst hydraulic loop can not satisfy all the load distribution condition. It can be concluded that the optimal reset method provides better adaptability and energy saving effect than other common methods and the worst thermodynamic loop provides proper reference for optimization of HVAC water system control strategy.