HEALTH EFFECTS AMONG PUPILS AFTER CHANGING THE SUPPLY AIR INLET FROM MIXING CEILING SYSTEM TO FLOOR LEVEL DISPLACEMENT SYSTEM- AN EXPERIMENTAL STUDY IN A SWEDISH PRIMARY SCHOOL

Dan Norback,Gunilla Wieslander,Zhuohui Zhao
2009-01-01
Abstract:We studied health effects when changing from mixing ceiling ventilation to two types of displacement supply air devices (FVS and FMS).. One classroom had changes, two others served as controls. The medical investigation included tear film stability (BUT), nasal patency. and a questionnaire. When changing from mixing to FVS, mean CO(2) levels was reduced from 810 to 610 ppm, and formaldehyde levels were reduced from 18 to 10 mu g/m(3) Levels of viable bacteria was higher (2100 cfu/m(3)) with ceiling ventilation, as compared to 3 FVS 475 cfu/m(3). When changing from ceiling ventilation to FVS, the pupils (N=26) perceived better air quality (p=0.006), and less dyspnoea (p=0.007) as compared to controls (N=35), and BUT was improved (p=0.03). In conclusion, displacement ventilation (FMS or FVS) in schools may lead to health improvements among primary school pupils, as compared to a conventional mixing system with supply air ducts at the ceiling.