Investigation on the Influence of EEV Opening on the Reliability of an R290 ASHP During Defrosting

Yanjun Du,Jianhua Wu,Che Wang,Rui Chen,Jinbo Li
DOI: https://doi.org/10.1016/j.enbuild.2020.110218
IF: 7.201
2020-01-01
Energy and Buildings
Abstract:In the defrosting process, it is not that the larger the opening of throttle valve is, the better for defrosting. Especially in the defrosting process of R290 heat pump, too small opening or large opening will affect the defrosting performance, and even cause oil blockage. In this paper, the defrosting characteristics of an R290 air source heat pump (ASHP) with different throttle valve opening are studied. The experimental results show that the defrosting duration will increase with the increase of the throttle valve opening. In addition, when the throttle valve opening was 120, oil blockage occurred in defrosting process, while when the opening was 480, oil blockage occurred in startup of reheating process. The factors that affect the reliability of R290 ASHP in heating-defrosting operation include not only the migration of lubricating oil, but also the thermal inertia of the system after defrosting process. In the defrosting process of R290 ASHP, the selection of throttle valve opening is very important for its safety and reliability under the heating-defrosting condition. The results of this paper will provide an effective guidance for the selection of throttle valve opening of R290 ASHP in defrosting process. (c) 2020 Elsevier B.V. All rights reserved.
What problem does this paper attempt to address?