Development of an Adaptation Table to Enhance the Accuracy of the Predicted Mean Vote Model

Yu Li,Yacine Rezgui,Annie Guerriero,Xingxing Zhang,Mengjie Han,Sylvain Kubicki,Da Yan
DOI: https://doi.org/10.1016/j.buildenv.2019.106504
IF: 7.093
2020-01-01
Building and Environment
Abstract:The Predicted Mean Vote (PMV) model is extensively used by current thermal comfort standards, such as ASHRAE 55 and ISO 7730, despite its discrepancy in predicting Thermal Sensation (TS). The implicit assumption is that PMV can be applied for predicting TS of a large population. Our statistical analysis of a subset of ASHRAE global database of thermal comfort field study shows that occupants' expectations towards TS are affected by factors that are not accounted for in the classic PMV model, such as climate, building type, age group, season and gender. The influences of the climate and building type are more determinant. An adapted PMV (PMVa) model and an adaptation table were developed based on the selected samples to reduce this discrepancy. After adaptation, the medians of each category corresponding to the discrepancy are zero or near zero. The results also show that the adapted PMV outperforms the classic PMV in predicting TS, while increasing the overall accuracy from 36% to 39%.
What problem does this paper attempt to address?